Shadow

Application

Monitoring of the water level within an underground coal mine.

Key Requirements

  • Certified for use within an underground coal mine (potential for methane gas)
  • Analogue output to measure up to 30m of water depth
  • Facility for cable and catenary connection to lower the transmitter 300m down a bore
  • High accuracy and repeatability
  • Sensor referenced to atmosphere

Solution

STS ATM.ECO/N/Ex submersible pressure transmitter with the following key features;

  • IECEx certification
  • 4-20mA output with 3X overpressure on a 0-30m range transducer
  • 330m intrinsically safe ‘blue’ cabling with Viton seals and catenary fittings on the rear of the stainless steel housing
  • 0.1% FS accuracy with temperature compensation from -5 to 80 deg C
  • Sensor referenced to atmosphere via an integrated ‘breathing’ filter